ABB RELION 670 Series Technical Manual page 838

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 14
Control
Local panel switch
The local panel switch is a switch that defines the operator place selection. The switch connected
to this function can have three positions (remote/local/off). The positions are here defined so
that remote means that operation is allowed from station and/or remote level and local means
that operation is allowed from the IED level. The local/remote switch is also on the control/
protection IED itself, which means that the position of the switch and its validity information are
connected internally, not via I/O boards. When the switch is mounted separately from the IED the
signals are connected to the function via I/O boards.
When the local panel switch (or LHMI selection, depending on the set source to select this) is in Off
position, all commands from remote and local level will be ignored. If the position for the local/
remote switch is not valid the PSTO output will always be set to faulty state (3), which means no
possibility to operate.
To adapt the signals from the local HMI or from an external local/remote switch, the function
blocks LOCREM and LOCREMCTRL are needed and connected to QCBAY.
Permitted Source To Operate (PSTO)
The actual state of the operator place is presented by the value of the Permitted Source To
Operate, PSTO signal. The PSTO value is evaluated from the local/remote switch position
according to Table 482. In addition, there are two parameters that affect the value of the PSTO
signal.
If the parameter
value is set to 5 (all), that is, it is permitted to operate from both local and remote level without
any priority. When the external panel switch is in Off position the PSTO value shows the actual
state of the switch that is, 0. In this case it is not possible to control anything
If the parameter
value is set to 2 (Station or Remote), that is, it is permitted to operate from both station and
remote level without any priority.
Table 482: PSTO values for different Local panel switch positions
Local panel
switch
positions
0 = Off
1 = Local
1 = Local
2 = Remote
2 = Remote
2 = Remote
2 = Remote
3 = Faulty
832
AllPSTOValid is set and LR-switch position is in Local or Remote state, the PSTO
RemoteIncStation is set and the LR-switch position is in Remote state, the PSTO
PSTO
AllPSTOValid
RemoteInc
value
(setting
Station
parameter)
(setting
parameter)
0
-
-
1
Priority
-
5
No priority
-
6
Priority
No
7
Priority
No
2
Priority
Yes
5
No priority
-
3
-
-
LocSta.CtlV
Possible
al
locations that
(command)
shall be able
to operate
-
Not possible
to operate
-
Local Panel
-
Local or
Remote level
without any
priority
TRUE
Station level
FALSE
Remote level
-
Station or
Remote level
-
Local,
Station or
Remote level
without any
priority
-
Not possible
to operate
1MRK 502 066-UUS B
M13446-7 v7
M13446-16 v8
Technical manual