Section 18
Station communication
18.13.2
Functionality
GOOSEMVRCV is used to receive measured value using IEC61850 protocol via GOOSE.
18.13.3
Function block
BLOCK
IEC10000251 V1 EN-US
Figure 612: GOOSEMVRCV function block
18.13.4
Signals
Table 916: GOOSEMVRCV Input signals
Name
BLOCK
Table 917: GOOSEMVRCV Output signals
Name
MVOUT
DATAVALID
COMMVALID
TEST
18.13.5
Settings
Table 918: GOOSEMVRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
18.13.6
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total failure condition
and the GOOSE transmission from the sending IED does not happen.
1202
GOOSEMVRCV
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251-1-en.vsd
Type
BOOLEAN
Type
REAL
BOOLEAN
BOOLEAN
BOOLEAN
Unit
-
Default
Description
0
Block of function
Description
Measurand value output
Data valid for measurand value output
Communication valid for measurand value output
Test output
Step
Default
-
Disabled
1MRK 502 066-UUS B
GUID-759CB016-2B4D-4D98-82E1-592044983D53 v2
GUID-A0B333CC-AEF4-40EA-B152-364648AB78D3 v1
Description
Operation Disabled/Enabled
GUID-7B24A6D3-2E5F-4961-A0A6-86436373809E v3
Technical manual
PID-2530-INPUTSIGNALS v18
PID-2530-OUTPUTSIGNALS v18
PID-2530-SETTINGS v18