The DC input is protected against inverse polarity within the rated DC voltage range.
Connection diagram
IEC08000476 V2 EN-US
Figure 646: PSM Connection diagram.
22.2.3.3
Technical data
Table
1002:
Quantity
Auxiliary dc voltage, EL (input)
Power consumption
Auxiliary DC power in-rush
22.2.4
Local human-machine interface (Local HMI)
Refer to section
22.2.5
Transformer input module (TRM)
22.2.5.1
Introduction
The transformer input module is used to galvanically separate and adapt the secondary currents
and voltages generated by the measuring transformers. The module has twelve inputs in different
combinations of currents and voltage inputs. Either protection class or metering class CT inputs
are available.
Alternative connectors of Ring lug or Compression type can be ordered.
22.2.5.2
Design
The transformer module has 12 input transformers. There are several versions of the module, each
with a different combination of voltage and current input transformers.
Basic versions:
Technical manual
PSM - Power supply module
""
for information.
Rated value
EL = (24 - 60) V
EL = (90 - 250) V
50 W typically
< 10 A during 0.1 s
Section 22
IED hardware
M6377-8 v2
SEMOD52801-1 v1
M12286-1 v4
Nominal range
EL ±20%
EL ±20%
-
-
SEMOD56218-5 v2
IP15581-1 v1
M14875-3 v9
M14858-3 v8