ABB RELION 670 Series Technical Manual page 1024

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 16
Monitoring
Name
Values (Range)
QDbRepInt
1 - 300
QZeroDb
0 - 100000
QHiHiLim
-2000.0 - 2000.0
QHiLim
-2000.0 - 2000.0
QLowLim
-2000.0 - 2000.0
QLowLowLim
-2000.0 - 2000.0
QLimHyst
0.000 - 100.000
PFDbRepInt
1 - 300
PFZeroDb
0 - 100000
PFHiHiLim
-1.000 - 1.000
PFHiLim
-1.000 - 1.000
PFLowLim
-1.000 - 1.000
PFLowLowLim
-1.000 - 1.000
PFLimHyst
0.000 - 100.000
VDbRepInt
1 - 300
VZeroDb
0 - 100000
VHiHiLim
0.0 - 200.0
VHiLim
0.0 - 200.0
VLowLim
0.0 - 200.0
VLowLowLim
0.0 - 200.0
VLimHyst
0.000 - 100.000
IDbRepInt
1 - 300
IZeroDb
0 - 100000
IHiHiLim
0.0 - 500.0
IHiLim
0.0 - 500.0
ILowLim
0.0 - 500.0
ILowLowLim
0.0 - 500.0
ILimHyst
0.000 - 100.000
FrDbRepInt
1 - 300
FrZeroDb
0 - 100000
FrHiHiLim
0.000 - 100.000
FrHiLim
0.000 - 100.000
FrLowLim
0.000 - 100.000
Table continues on next page
1018
Unit
Step
Default
Type
1
10
m%
1
500
%SB
0.1
150.0
%SB
0.1
120.0
%SB
0.1
-120.0
%SB
0.1
-150.0
%
0.001
5.000
Type
1
10
m%
1
500
-
0.001
1.000
-
0.001
0.800
-
0.001
-0.800
-
0.001
-1.000
%
0.001
5.000
Type
1
10
m%
1
500
%VB
0.1
150.0
%VB
0.1
120.0
%VB
0.1
80.0
%VB
0.1
60.0
%
0.001
5.000
Type
1
10
m%
1
500
%IB
0.1
150.0
%IB
0.1
120.0
%IB
0.1
80.0
%IB
0.1
60.0
%
0.001
5.000
Type
1
10
m%
1
500
Hz
0.001
65.000
Hz
0.001
63.000
Hz
0.001
47.000
1MRK 502 066-UUS B
Description
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping in 0.001% of range
High High limit in % of SBase
High limit in % of SBase
Low limit in % of SBase
Low Low limit in % of SBase
Hysteresis value in % of range (common
for all limits)
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping in 0.001% of range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Hysteresis value in % of range (common
for all limits)
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping in 0.001% of range
High High limit in % of UBase
High limit in % of VBase
Low limit in % of VBase
Low Low limit in % of VBase
Hysteresis value in % of range (common
for all limits)
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping in 0.001% of range
High High limit in % of IBase
High limit in % of IBase
Low limit in % of IBase
Low Low limit in % of IBase
Hysteresis value in % of range (common
for all limits)
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Zero point clamping in 0.001% of range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)