ABB RELION 670 Series Technical Manual page 1217

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
Section 19
19.1
Binary signal transfer
19.1.1
Identification
Function description
19.1.2
Functionality
The remote end data communication is used either for the transmission of current values with a
maximum of 8 binary signals in the line differential protection IED, or for the transmission of only
binary signals (up to 192) in the other IEDs. The binary signals are freely configurable and can, thus,
be used for any purpose, for example, communication scheme related signals, transfer trip and/or
other binary signals between IEDs.
Communication between two IEDs requires that each IED is equipped with a Line Data
Communication Module (LCDM). The LDCMs then act as interfaces to a 64 kbit/s communication
channel for duplex communication between the IEDs.
The IED can be equipped with up to two short range or medium range LDCMs.
Technical manual
Remote communication
Binary signal transfer
Binary signal transfer
IEC 61850
IEC 60617
identification
identification
BinSignReceive
-
BinSignTransm
-
Remote communication
ANSI/IEEE C37.2
device number
-
-
Section 19
IP12423-1 v2
M14849-1 v2
SEMOD52522-4 v5
1211