ABB RELION 670 Series Technical Manual page 1206

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 18
Station communication
The TEST output will go HIGH if the sending IED is in test mode.
18.12
GOOSE function block to receive an integer value
GOOSEINTRCV
18.12.1
Identification
Function description
GOOSE function block to receive an
integer value
18.12.2
Functionality
GOOSEINTRCV is used to receive an integer value using IEC61850 protocol via GOOSE.
18.12.3
Function block
BLOCK
IEC10000250 V1 EN-US
Figure 611: GOOSEINTRCV function block
18.12.4
Signals
Table 913: GOOSEINTRCV Input signals
Name
BLOCK
1200
The input of this GOOSE block must be linked in SMT by means of a cross to receive
the double point values.
The implementation for IEC61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA
then the DATAVALID output will be LOW.
GOOSEINTRCV
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250-1-en.vsd
Type
BOOLEAN
IEC 61850
IEC 60617
identification
identification
GOOSEINTRCV
-
Default
Description
0
Block of function
1MRK 502 066-UUS B
GUID-93A1E81B-1DE8-483A-BB3B-DB771EE66DC1 v1
ANSI/IEEE C37.2
device number
-
GUID-27B1ED7A-C8E8-499E-89C1-C656FB0337F8 v2
GUID-56F0C9F7-98F3-4091-B071-53CA5074DC8F v1
PID-2529-INPUTSIGNALS v18
Technical manual