Section 14
Control
The execute output pulses are reset when:
the new expected final position is reached and the configuration parameter
set to true
the timer
an error occurs due to the switch does not start moving, that is,
There is one exception from the first item above. If the primary device is in open position and an
open command is executed or if the primary device is in closed position and a close command is
executed. In these cases, with the additional condition that the configuration parameter
AdaptivePulse is true, the execute output pulse is always activated and resets when tStartMove
has elapsed. If the configuration parameter
remains active until the pulse duration timer has elapsed.
An example of when a primary device is open and an open command is executed is shown in
Figure
448
OPENPOS
CLOSEPOS
EXE_OP
EXE_OP
tStartMove timer
IEC05000099 V1 EN-US
Figure 448: Open command with open position indication
14.3.8
Circuit switch SXSWI
850
tOpenPulse or tClosePulse has elapsed
If the breaker reaches the final position before the execution pulse time has
AdaptivePulse is not true, the function waits for the end of the
elapsed, and
execution pulse before telling the activating function that the command is
completed.
If the start position indicates bad state (OPENPOS=1 and CLOSEPOS =1) when a
command is executed the execute output pulse resets only when timer
tClosePulse has elapsed.
or
.
tOpenPulse
tOpenPulse
AdaptivePulse is set to false the execution output
AdaptivePulse=FALSE
AdaptivePulse=TRUE
en05000099.vsd
1MRK 502 066-UUS B
AdaptivePulse is
tStartMove has elapsed.
tOpenPulse
Technical manual