1MRK 502 066-UUS B
Table 942: Default users
User name
SuperUser
Guest
Administrator
Table 943: Predefined user roles according to IEC 62351-8
User roles
VIEWER
OPERATOR
ENGINEER
INSTALLER
SECADM
SECAUD
RBACMNT
ADMINISTRATOR
The successfully activation of Central Account Management will disable built-in users or remove all
local created users from PCM600.
Management of user credentials and roles is handled on the central Account Management server
e.g. SDM600 The IED employs two strategies to ensure availability of the authentication system
even if there is a problem with the network or authentication server:
Technical manual
User rights
Full rights, only presented in LHMI. LHMI is logged on by default until other users are defined
Only read rights, only presented in LHMI. LHMI is logged on by default when other users are
defined (same as VIEWER)
Full rights. Password: Administrator. This user has to be used when reading out disturbances
with third party FTP-client.
Role explanation User rights
Viewer
Can read parameters and browse the menus from LHMI
Operator
Can read parameters and browse the menus as well as perform control
actions
Engineer
Can create and load configurations and change settings for the IED and
also run commands and manage disturbances
Installer
Can load configurations and change settings for the IED
Security
Can change role assignments and security settings. Can deploy
administrator
certificates.
Security auditor
Can view audit logs
RBAC
Can change role assignment
management
Administrator
Sum of all rights for SECADM, SECAUD and RBACMNT
rights
Changes in user management settings do not cause an IED reboot.
The PCM600 tool caches the login credentials after successful login for 15 minutes.
During that time no more login will be necessary.