ABB RELION 670 Series Technical Manual page 514

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 8
Current protection
8.6.5
Settings
Table 244: SDEPSDE (67N) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpModeSel
3I0Cosfi
3I03V0Cosfi
3I0 and fi
DirMode
Forward
Reverse
RCADir
-179 - 180
RCAComp
-10.0 - 10.0
ROADir
0 - 90
INCosPhiPU
0.25 - 200.00
SN_PU
0.25 - 200.00
INDirPU
0.25 - 200.00
tDef
0.000 - 60.000
SRef
0.03 - 200.00
TDSN
0.00 - 2.00
OpINNonDir
Disabled
Enabled
INNonDirPU
1.00 - 400.00
tINNonDir
0.000 - 60.000
TimeChar
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
Table continues on next page
508
Unit
Step
Default
-
-
Disabled
-
-
3I0Cosfi
-
-
Forward
Deg
1
-90
Deg
0.1
0.0
Deg
1
90
%IB
0.01
1.00
%SB
0.01
10.00
%IB
0.01
5.00
s
0.001
0.100
%SB
0.01
10.00
-
0.01
0.10
-
-
Disabled
%IB
0.01
10.00
s
0.001
1.000
-
-
IEC Norm. inv.
1MRK 502 066-UUS B
Description
Operation Disabled/Enabled
Selection of operation mode for
protection
Direction of operation forward or reverse
Relay characteristic angle RCA, in deg
Relay characteristic angle compensation
Relay open angle ROA used as release in
phase mode, in deg
Set level for 3I0cosFi, directional res over
current in % of IBase
Set level for 3I03U0cosFi, starting inv time
count in % of SBase
Set level for directional residual over
current prot in % of IBase
Definite time delay directional residual
overcurrent, in sec
Reference value of res power for inverse
time count in % of SBase
Time multiplier setting for directional
residual power mode
Operation of non-directional residual
overcurrent protection
Set level for non directional residual over
current in % of IBase
Time delay for non-directional residual
over current, in sec
Operation curve selection for IDMT
operation
Technical manual
PID-3892-SETTINGS v6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reg670

Table of Contents