ABB RELION 670 Series Technical Manual page 376

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 7
Impedance protection
Name
SLIPZPER
VCOS
VCOSPER
7.10.5
Settings
Table 158: PSPPPAM (78) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OperationZ1
Disabled
Enabled
OperationZ2
Disabled
Enabled
ImpedanceZA
0.00 - 1000.00
ImpedanceZB
0.00 - 1000.00
ImpedanceZC
0.00 - 1000.00
AnglePhi
72.00 - 90.00
pick up Angle
0.0 - 180.0
TripAngle
0.0 - 180.0
N1Limit
1 - 20
N2Limit
1 - 20
Table 159: PSPPPAM (78) Group settings (advanced)
Name
Values (Range)
ResetTime
0.000 - 60.000
Table 160: PSPPPAM (78) Non group settings (basic)
Name
Values (Range)
MeasureMode
PosSeq
AB
BC
CA
InvertCTcurr
No
Yes
GlobalBaseSel
1 - 12
370
Type
Description
REAL
Slip impedance in percent of ZBase
REAL
UCosPhi voltage
REAL
VCosPhi voltage in percent of VBase
Unit
Step
-
-
-
-
-
-
%
0.01
%
0.01
%
0.01
Deg
0.01
Deg
0.1
Deg
0.1
-
1
-
1
Unit
Step
s
0.001
Unit
Step
-
-
-
-
-
1
Default
Description
Disabled
Operation Enable / Disable
Enabled
Operation Enable/Disable zone Z1
Enabled
Operation Enable/Disable zone Z2
10.00
Forward impedance in % of Zbase
10.00
Reverse impedance in % of Zbase
10.00
Impedance of zone1 limit in % of Zbase
85.00
Angle of the slip impedance line
110.0
Rotor angle for the pickup signal
90.0
Rotor angle for the trip1 and trip2 signals
1
Count limit for the trip1 signal
3
Count limit for the trip2 signal
Default
Description
5.000
Time without slip to reset all signals
Default
Description
PosSeq
Measuring mode (PosSeq, AB, BC, CA)
No
Invert current direction
1
Selection of one of the Global Base Value
groups
1MRK 502 066-UUS B
PID-3526-SETTINGS v3