Section 7
Impedance protection
Name
Values (Range)
X1FwPGZ4
0.01 - 3000.00
R1FwPGZ4
0.00 - 1000.00
X0FwPGZ4
0.01 - 9000.00
R0FwPGZ4
0.00 - 3000.00
RFFwPGZ4
0.01 - 9000.00
X1RvPGZ4
0.01 - 3000.00
RFRvPGZ4
0.01 - 9000.00
tPPZ4
0.000 - 60.000
tPGZ4
0.000 - 60.000
IMinOpPPZ4
10 - 6000
IMinOpPGZ4
5 - 6000
OpModePPZ5
Disabled
Quadrilateral
Mho
MhoOffset
OpModePGZ5
Disabled
Quadrilateral
Mho
MhoOffset
DirModeZ5
Non-directional
Forward
Reverse
X1FwPPZ5
0.01 - 3000.00
R1FwPPZ5
0.00 - 1000.00
RFFwPPZ5
0.01 - 9000.00
X1RvPPZ5
0.01 - 3000.00
RFRvPPZ5
0.01 - 9000.00
X1FwPGZ5
0.01 - 3000.00
R1FwPGZ5
0.00 - 1000.00
X0FwPGZ5
0.01 - 9000.00
R0FwPGZ5
0.00 - 3000.00
Table continues on next page
336
Unit
Step
Default
Ohm/p
0.01
40.00
Ohm/p
0.01
5.00
Ohm/p
0.01
120.00
Ohm/p
0.01
15.00
Ohm/l
0.01
100.00
Ohm/p
0.01
40.00
Ohm/l
0.01
100.00
s
0.001
1.200
s
0.001
1.200
%IB
1
10
%IB
1
10
-
-
Quadrilateral
-
-
Quadrilateral
-
-
Forward
Ohm/p
0.01
40.00
Ohm/p
0.01
5.00
Ohm/l
0.01
30.00
Ohm/p
0.01
40.00
Ohm/l
0.01
30.00
Ohm/p
0.01
40.00
Ohm/p
0.01
5.00
Ohm/p
0.01
120.00
Ohm/p
0.01
15.00
1MRK 502 066-UUS B
Description
Positive seq. reactance reach, Ph-G, zone 4,
zone direction
Positive seq. resistive reach, Ph-G, zone 4,
zone direction
Zero seq. reactance reach, Ph-G, zone 4,
zone direction
Zero seq. resistive reach, Ph-G, zone 4,
zone direction
Fault resistance reach, Ph-G, zone 4, zone
direction
Pos. seq. react. reach, Ph-G, zone 4,
opposite to zone dir
Fault resistance reach, Ph-G, zone 4,
opposite to zone dir.
Time delay to trip, Phase-Phase, zone 4
Time delay to trip, Phase-ground, zone 4
How start of trip delay timers should be
linked for zone 4
Minimum operate phase current for phase-
ground loops, zone 4
Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 5
Enabled/Disabled and characteristic
setting for Ph-G loops, zone 5
Direction of zone 5 (which will be the Fw
direction of zone 5)
Positive seq. reactance reach, Ph-Ph, zone
5, zone direction
Positive seq. resistive reach, Ph-Ph, zone 5,
zone direction
Fault resistance reach, Ph-Ph, zone 5, zone
direction
Pos. seq. react. reach, Ph-Ph, zone 5,
opposite to zone dir
Fault resistance reach, Ph-Ph, zone 5,
opposite to zone dir.
Positive seq. reactance reach, Ph-G, zone 5,
zone direction
Positive seq. resistive reach, Ph-G, zone 5,
zone direction
Zero seq. reactance reach, Ph-G, zone 5,
zone direction
Zero seq. resistive reach, Ph-G, zone 5,
zone direction
Technical manual