ABB RELION 670 Series Technical Manual page 317

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

1MRK 502 066-UUS B
b
=
arg
ANSIEQUATION15027 V1 EN-US
where
V
AB
ANSI V1 EN-US
EQUATION1790-
I
AB
ANSI V1 EN-US
EQUATION1791-
1
Z
set
For Zone 1,
Z
1
=
set
IECEQUATION15011 V1 EN-US
where
R1PPZ1
X1PPZ1
For Zone 2-5 and RV
Z
1
=
set
IECEQUATION15012 V1 EN-US
where
R1Zx
X1Zx
V
pol
Operation occurs if 90°≤β≤270°
Technical manual
(
)
-
×
-
V
I
Z
1
arg
AB
AB
set
is the voltage vector difference between phases A and B
is the current vector difference between phases A and B
is the positive sequence impedance setting for phase-to-phase fault in zone direction
R PPZ
1
1
j X PPZ
1
1
+ ⋅
is the positive sequence resistive reach for phase-to-phase fault for zone 1
is the positive sequence reactance reach for phase-to-phase fault for zone 1
R Zx
1
j X Zx
1
+ ⋅
is the positive sequence resistive reach for zone x (x=2-5 and RV)
is the positive sequence reactance reach for zone x (x=2-5 and RV)
is the polarizing voltage
( )
V
p
ol
Section 7
Impedance protection
(Equation 84)
(Equation 85)
(Equation 86)
311