ABB RELION 670 Series Technical Manual page 340

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 7
Impedance protection
Name
Values (Range)
IMinOpPPZ1
10 - 6000
IMinOpPGZ1
5 - 6000
OpModePPZ2
Disabled
Quadrilateral
Mho
MhoOffset
OpModePGZ2
Disabled
Quadrilateral
Mho
MhoOffset
X1FwPPZ2
0.01 - 3000.00
R1FwPPZ2
0.00 - 1000.00
X1RvPPZ2
0.01 - 3000.00
X1FwPGZ2
0.01 - 3000.00
R1FwPGZ2
0.00 - 1000.00
X0FwPGZ2
0.01 - 9000.00
R0FwPGZ2
0.00 - 3000.00
X1RvPGZ2
0.01 - 3000.00
RFPPZ2
0.01 - 9000.00
RFPGZ2
0.01 - 9000.00
tPPZ2
0.000 - 60.000
tPGZ2
0.000 - 60.000
IMinOpPPZ2
10 - 6000
IMinOpPGZ2
5 - 6000
OpModePPZ3
Disabled
Quadrilateral
Mho
MhoOffset
OpModePGZ3
Disabled
Quadrilateral
Mho
MhoOffset
DirModeZ3
Non-directional
Forward
Reverse
X1FwPPZ3
0.01 - 3000.00
Table continues on next page
334
Unit
Step
Default
%IB
1
10
%IB
1
10
-
-
Quadrilateral
-
-
Quadrilateral
Ohm/p
0.01
40.00
Ohm/p
0.01
5.00
Ohm/p
0.01
40.00
Ohm/p
0.01
40.00
Ohm/p
0.01
5.00
Ohm/p
0.01
120.00
Ohm/p
0.01
15.00
Ohm/p
0.01
40.00
Ohm/l
0.01
30.00
Ohm/l
0.01
100.00
s
0.001
0.400
s
0.001
0.400
%IB
1
10
%IB
1
10
-
-
Quadrilateral
-
-
Quadrilateral
-
-
Forward
Ohm/p
0.01
40.00
1MRK 502 066-UUS B
Description
Minimum operate ph-ph current for Phase-
Phase loops, zone 1
minimum operate phase current for phase-
ground loops. zone 1
Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 2
Enabled/Disabled and characteristic
setting for Ph-G loops, zone 2
Positive seq. reactance reach, Ph-Ph, zone
2, forward dir.
Positive seq. resistive reach, Ph-Ph, zone 2,
forward dir.
Pos. seq. react. reach, Ph-Ph, zone 2,
reverse direction
Positive seq. reactance reach, Ph-G, zone 2,
forward dir.
Positive seq. resistive reach, Ph-G, zone 2,
forward dir.
Zero seq. reactance reach, Ph-G, zone 2,
forward direction
Zero seq. resistive reach, Ph-G, zone 2,
forward direction
Pos. seq. react. reach, Ph-G, zone 2, reverse
direction
Zero sequence reactance reach, zone 2
Fault resistance reach, Ph-g, Zone 2
Time delay to trip, Phase-Phase, zone 2
Time delay to trip, Phase-Ground, zone 2
Time delay to trip, Phase-Phase, zone 2
Minimum operate phase current for phase
- ground loops, zone 2
Enabled/Disabled and characteristic
setting for Ph-Ph loops, zone 3
Enabled/Disabled and characteristic
setting for Ph-G loops, zone 3
Time delay to trip, Phase-Phase, zone 2
Positive seq. reactance reach, Ph-Ph, zone
3, zone direction
Technical manual