Signals - ABB RELION 670 Series Technical Manual

Generator protection
Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Section 7
Impedance protection
7.11.4

Signals

Table 163: OOSPPAM (78) Input signals
Name
I3P1
I3P2
V3P
BLOCK
BLKGEN
BLKMOT
EXTZ1
Table 164: OOSPPAM (78) Output signals
Name
TRIP
TRIPZ1
TRIPZ2
PICKUP
GENMODE
MOTMODE
R
X
SLIPFREQ
ROTORANG
VCOSPHI
376
Type
Default
Description
GROUP
-
Group connection for three-phase current input 1
SIGNAL
GROUP
-
Group connection for three-phase current input 2
SIGNAL
GROUP
-
Group connection for three-phase voltage input
SIGNAL
BOOLEAN
0
Block of function
BOOLEAN
0
Block operation in generating direction
BOOLEAN
0
Block operation in motor direction
BOOLEAN
0
Extension of zone1 reach to zone2 settings
Type
Description
BOOLEAN
Common trip, issued when either zone 1 or zone 2 trip
BOOLEAN
Zone 1 trip
BOOLEAN
Zone 2 trip
BOOLEAN
Set when measured impedance enters lens characteristic
BOOLEAN
Generator rotates faster than the system during pole slip
BOOLEAN
Generator rotates slower than the system during pole slip
REAL
Real part of measured positive-sequence impedance % of VBase/
(sqrt(3)*IBase)
REAL
Imaginary part of measured positive-seq impedance % of VBase/
(sqrt(3)*IBase)
REAL
Slip frequency in Hz
REAL
Rotor angle as estimated by the out-of-step function
REAL
Estimated Ucos(Phi) voltage during pole slip, in V
1MRK 502 066-UUS B
PID-3539-INPUTSIGNALS v9
PID-3539-OUTPUTSIGNALS v9
Technical manual