Power Supply Wiring
This section describes how to connect the power supply cable. Make sure to read this
section before wiring the power supplly cables.
100 to 120 VAC/200 to 240 VAC Power Supply Model
Precautions to be taken when wiring the power supply
To prevent electric shock and damage to the recorder, observe the following warnings.
• Confirm that the supply voltage meets the rated power supply voltage before
• Confirm that the power is turned OFF before connecting the power cord.
• To prevent electric shock and the possibility of fire, use only the power cord that
• Always use protective earth terminal to prevent electric shock. Connect the
• Never use an extension cord that does not have protective earth terminal,
Use a power supply that meets the following conditions:
Item
Rated power supply
Allowable power supply voltage range
Rated power supply frequency
Allowable power supply frequency range
Maximum power consumption
Note
• Connection procedure
1.
2.
3.
connecting the cable.
is supplied by Omega.
power cord to a three-pole power outlet that has a protective earth terminal.
otherwise the protection function will be compromised.
Do not use a supply voltage in the range 132 to 180 VAC, as this may have adverse effects
on the measurement accuracy.
Check that the recorder is turned OFF.
Connect the power cable (supplied with the recorder) to the power connector on
the rear panel of the recorder.
Connect the other end of the power cord to a socket that meets the
requirements.
WARNING
Conditions
100 to 240 VAC
90 to 132 or 180 to 264 VAC
50/60 Hz
50/60 Hz±2%
38 VA(100 V), 53 VA(240 V)
2
2-13