10.7 Setting the Remote Control Functions (Option, /R1, Basic Setting Mode)
• Pnl 1 to Pnl 3 load
• Remote input : Trigger, 250 ms or more
• The setup data of the file "LOAD 1.PNL," "LOAD 2.PNL," or "LOAD 3.PNL" that is
saved in the external storage medium are loaded for use. The file, "LOAD 1.PNL,"
"LOAD 2.PNL," or "LOAD 3.PNL" must be created and saved to the external
storage medium beforehand.
• Message 1 to message 8
• Remote input : Trigger, 250 ms or more
• Displays a message at the position corresponding to the time when the signal was
applied on the trend display. The displayed message is also written to the internal
memory. When the data acquisition to the internal memory is stopped, messages
cannot be displayed or written. Applying a remote signal produces no effect.
Remote input signal
The above operations are carried out on the rising or falling edge of the remote signal
(edge) or the ON signal lasting at least 250 ms (trigger).
Rising/Falling
Rising
Falling
For contact inputs, the remote signal rises when the contact switches from open to
closed and falls when the contact switches from closed to open. For open collector
signals, the remote signal rises when the collector signal (voltage level of the remote
terminal) goes from high to low and falls when the collector signal goes low to high.
Trigger
250 ms or more