10.7 Setting the Remote Control Functions (Option, /R1, Basic Setting Mode)
10-12
• Start/Stop
• Remote input : Rising/start, falling/stop
• Start
Starts/stops the acquisition of the display data and the event data, the computation
(option) , and the report (option).
• Stop
Stops the acquisition of the display data and the event data, and the report
(option).
• If the RD-MV100 is started, applying a rising signal produces no effect. If the RD-
MV100 is stopped, applying a falling signal produces no effect.
• Trigger
• Remote input : Trigger, 250 ms or more
• This becomes the external trigger that starts the acquisition of the event data to the
internal memory. This is valid only when acquiring the event data to the internal
memory using the trigger or rotate mode, the acquisition start trigger is set to
external trigger, and the RD-MV100 is in the trigger wait state (see section 8.2).
For all other cases, applying the remote signal produces no effect.
• Alarm ACK
• Remote input : Trigger, 250 ms or more
• Releases the alarm indication and relay output (option). This is the same function
as when the [Alarm ACK] soft key is pressed.
• Time adj
• Remote input : Trigger, 250 ms or more
• Adjusts the internal clock of the RD-MV100 to the nearest hour depending on the
time when the remote signal is applied.
Time of Signal Input
00 min. 00 s to 01 min. 59 s
02 min. 00 s to 57 min. 59 s
58 min. 00 s to 59 min. 59 s
• Math (option)
• Remote input : Rising/start, falling/stop
• Starts/stops the computation. This is valid only on models with the computation
function (/M1 option).
• If the computation is started, applying a rising signal produces no effect. If the
computation is stopped, applying a falling signal produces no effect.
• Math rst (option)
• Remote input : Trigger, 250 ms or more
• Resets the data on all computation channels. This is valid only on models with the
computation function (/M1 option) and while the computation is stopped. For all
other cases, applying the remote signal produces no effect.
• M. sample
• Remote input : Trigger, 250 ms or more
• The instantaneous values of all measurement and computation channels
(excluding the measurement channels that are set to [Skip] and the computation
channels that are turned Off) can be stored to the internal memory.
New Time
Adjusts the internal clock down to the nearest hour.
Example : 10 hr. 01 min. 50 s becomes 10 hr. 00 min. 00 s.
Time is unchanged.
Adjusts the internal clock down to the nearest hour.
Example : 10 hr. 59 min. 50 s becomes 11 hr. 00 min. 00 s.