Omega RD-MV100 Series User Manual page 258

Hide thumbs Also See for RD-MV100 Series:
Table of Contents

Advertisement

• The reading error is large.
• The digital indication or trend trace (waveform) is unstable.
• The trend trace (waveform) stays at 0 or 100%.
Does the input
meet the specifications
(signal source resistance,
etc.)?
YES
Are the span and
range settings correct?
YES
Is the input free of noise?
YES
Is the environmental
temperature kept constant
(for temperature
measurement)?
YES
Is the input wiring correct?
YES
Is the input wiring parallel
with other equipment?
NO
Is the RJC setting correct
(for TC input)?
YES
Contact Omega.
12.2 Troubleshooting Flow Chart
NO
Change the input to meet the specifications
(See section 14.1).
NO
Adjust the span and range
(See sections 5.1 to 5.7).
• Separate the input wiring from the
noise source.
• Ground the recorder properly.
NO
• Ground the measuring object
properly.
• Insulate the TC from the measured
object.
• Use shielded cable for input.
• Correct the A/D integration frequency
(See section 5.9).
• Use the input filter (See section 5.8).
• Use the cover for the input terminal.
NO
• Protect the input terminal from wind
or fans.
• Keep the room temperature constant
around the input terminal.
• Wire correctly (See section 2.3).
NO
• Fix the terminal block properly.
• Fasten the terminal screws.
• Insulate the RTD from ground.
• If burnt, replace the TC.
• Stop the TC burnout
YES
upscale/downscale function of other
equipment.
• Ground the recorder and other
equipment at the same grounding
pole.
• Disconnect parallel wiring. (Use a
double-element TC, for instance.)
NO
Set correctly (See section 5.9).
12
12-9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rd-mv102Rd-mv104Rd-mv106Rd-mv112