Omega RD-MV100 Series User Manual page 108

Hide thumbs Also See for RD-MV100 Series:
Table of Contents

Advertisement

5.2
Thermocouple (TC)/Resistance Temperature
Detector (RTD) Setting
To measure TC and RTD signals, follow the procedures below to set the input range.
The range cannot be changed while data acquisition or computation is in progress.
Procedure
• These procedures are carried out in the setting mode.
• Use the arrow keys to move the cursor (blue) to the appropriate parameter. (The
parameters that cannot be changed are grayed.)
• The possible selections are displayed at the bottom of the screen. Select using the
soft keys.
• The parameter boxes that are changed are displayed in yellow. By confirming the
new settings, they change back to white.
Press
To display the setting screen press the soft key
2
2
The numbers in front of the operating procedure shown below correspond to the
numbers in the above figure.
1.
2.
3.
4.
Note
Span lower limit and span upper limit cannot be set to the same value.
MENU
.
1
4
3
1
3
4
First channel and last channel
Select the desired channels.
Mode
Set the mode to [TC] (thermocouple) or [RTD] (resistance temperature detector.
Range
Set the type of thermocouple or RTD.
Upper and lower limits of span
Set the upper and lower limits of the display span.
Pressing the [Input] soft key displays a window used to enter a numerical value.
Enter a value in the allowed range and press the DISP/ENTER key.
For the procedures related to entering numerical values, see "Entering
Numbers" on page 3-21.
#1
.
5
5-3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rd-mv102Rd-mv104Rd-mv106Rd-mv112

Table of Contents