6.2
Alarm Setting
This section describes the procedures related to setting the alarm specification on each
channel. The auxiliary alarm function are set in the basic setting mode. (See section 6.4)
Note
Procedure
• These procedures are carried out in the setting mode.
• Use the arrow keys to move the cursor (blue) to the appropriate parameter. (The
parameters that cannot be changed are grayed.)
• The possible selections are displayed at the bottom of the screen. Select using the
soft keys.
• The parameter boxes that are changed are displayed in yellow. Once new settings
are confirmed, they change back to white.
Press
To display the setting screen press the soft key
The numbers in front of the operating procedure shown below correspond to the
numbers in the above figure.
1.
2.
3.
Set the measurement range before setting the alarm.
All of the alarm settings of a channel are canceled in the following cases :
When the input type is changed (Volt, TC, etc.).
When the input range is changed.
When displaying the scale or computing the square root and the measurement span or
scaling value is changed (includes decimal position change).
If the range setting is set to [Skip], alarm setting is not possible. (The alarm setting boxes are
grayed in this case.)
MENU
.
1
3
4
5
6
2
First channel and last channel
Select the desired channels. (For the channels set here, [Range] is also
simultaneously set.)
On/Off
When the alarm is turned on, [Type], [Value], and [Relay On/Off] are displayed.
Type
Set the alarm type. For the alarm types, see "Explanation."
#1
.
6
6-5