Digital inputs
180
FlexTest IIm Controller Connections
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
•
Digital inputs can be wired to allow the input from a switch
contact, a relay contact, or a logic signal.
•
All digital inputs are optically isolated at the 498 Digital I/O
transition module.
•
For example, an action defined in the can be selected, in the
Station Setup window's Digital Input panel, as an Action
•
The digital inputs are used by the Digital Input process in the
MultiPurpose TestWare application. They can also be monitored
from the Station Manager application.
•
You can use the Event-Action Editor window to define an action
that occurs in response to a digital input event. The defined action
can then be selected in the Station Setup window's Digital Input
panel.
•
Sixteen jumpers located on the 498 Digital I/O transition module
allow each input to be configured for a relay contact or logic signal.
•
Each digital input connector on the built-in Digital I/O Access panel
(FlexTest IIm) supports two channels.
•
Each digital input supports a differential TTL to +30 V DC signal or
a switch or relay contact switching the on-board 12 V supply.
MTS 793 Controller Hardware
Need help?
Do you have a question about the FlexTest IIm and is the answer not in the manual?
Questions and answers