Interlock Jumper Plugs
497.05 Hydraulic
Control Panel
498 System
Digital I/O
176
FlexTest IIm Controller Connections
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Several jumper plugs must be installed to maintain the integrity of the
interlock chain. Each jumper plug represents a place where you can
add a custom connection to the interlock chain.
Any interlocks connected to the hydraulic control panel will generate a
hydraulic interlock which shuts down the hydraulic power supply.
This type of interlock shuts down all test stations.
•
Connector J52 requires a jumper plug to close the interlock chain.
•
If J26 is not connected, it needs a jumper plug.
•
Connectors J15A–J17C (Remote Interlock Inputs) each require a
jumper plug unless it is being used. Jumper both pins of each
connector.
Any interlock connected to the 498 System Digital I/O transition
module can generate a station interlock to disable pressure (the HSM)
to that station.
The 498 System Digital I/O transition module supports:
•
Four stations of Hydraulics On digital inputs
•
Four stations of Hydraulics Hi digital inputs
•
Four stations of Hydraulics Enables
•
Four stations of Remote Stop/Run outputs
•
Four stations of program interlocks
•
Four stations of auxiliary interlocks
•
Four stations of 497 interlock inputs
•
Four stations of 497 interlock outputs
•
Four stations of auxiliary interlock inputs
•
Four stations of auxiliary interlock outputs
•
Two spare digital inputs
•
Two spare digital outputs
The interlock connectors require jumpers under the following
conditions: