Initiating an Analog Channel
The following table shows the physical metrics of analog channels.
Table 2-18: Analog channel parameter combinations.
Type
Temperature
Radial shaft vibration
Position
Complementary Differential
Expansion
Piston Rod Drop (Average
Mode)
Piston Rod Drop (Triggered
Mode)
1
Casing vibration
Eccentricity
Gap
3
Other
1 For Casing vibration type, the Detection of "RMS" is recommended if the Math Method is "single integration".
2 Detection types are true types; PtP (true peak to peak), P ("true peak to peak" /2), RMS (true root mean square
averaging)
3 Analog measurement type Other does not allow a user defined EU. Instead an EU can be selected from the list of
predefined engineering units.
SKF Multilog On-Line System IMx-M
User Manual
Protection Module Configuration with IMx-M Manager
Math
EU
Method
-
C,
F
-
µm,
mils
-
mm,
mils,
µm
-
mm,
mils,
µm
-
mils,
µm
-
mils,
µm
2
None
m/s
(m/s^2),
g,
ips,
mm/s
Single
µm,
integration
ips,
mils,
mm/s
-
µm,
mils
-
mV
-
psi, bar, mbar, Pa, hPa,
kPa, MPa, kg/cm
cmHg, mA, A, mV, V, kV,
C, F, Deg, W, kW, MW,
kVA, %, mH, T, µm, mm,
mils, ips, m/s
2
Detection
-
PtP
-
-
-
-
P,
PtP,
RMS
P,
PtP,
RMS
PtP
-
-
2
,
2
(m/s^2), g
Protection
Channel
9 to 16
1 to 16
1 to 16
1 to 16 (involves
both channels of
a pair)
1 to 16
1 to 16
1 to 16
1 to 16
1 to 16
1 to 16
2 - 107