Introduction
This chapter describes the dual/teaching timer instructions that cyclically turn outputs on and off in the specified time interval.
Four dual timers are available and the ON/OFF duration can be selected from 1 ms up to 65,535 s.
Teaching timer instruction measures the ON duration of the start input for the teaching timer instruction and stores the measured
data to a designated data register, which can be used as a preset value for a timer instruction.

DTML (1-s Dual Timer)

DTML
*****

DTIM (100-ms Dual Timer)

DTIM
*****

DTMH (10-ms Dual Timer)

DTMH
*****

DTMS (1-ms Dual Timer)

DTMS
*****
EACHING
S1
S2
D1
*****
*****
*****
S1
S2
D1
*****
*****
*****
S1
S2
D1
*****
*****
*****
S1
S2
D1
*****
*****
*****
FC6A S
MICROS
ERIES
T
I
IMER
NSTRUCTIONS
While input is on, destination device D1 repeats to turn on and off for a
D2
duration assigned by devices S1 and S2, respectively.
When the input is off, D1 turns off.
The time range is 0 through 65,535 s.
While input is on, destination device D1 repeats to turn on and off for a
D2
duration assigned by devices S1 and S2, respectively.
When the input is off, D1 turns off.
The time range is 0 through 6,553.5 s.
While input is on, destination device D1 repeats to turn on and off for a
D2
duration assigned by devices S1 and S2, respectively.
When the input is off, D1 turns off.
The time range is 0 through 655.35 s.
While input is on, destination device D1 repeats to turn on and off for a
D2
duration assigned by devices S1 and S2, respectively.
When the input is off, D1 turns off.
The time range is 0 through 65.535 s.