IDEC MICROSmart FC6A Series Ladder Programming Manual page 318

Automation organizer windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

18: P
O
I
ULSE
UTPUT
NSTRUCTIONS
RAMP1 instruction (reversible control enabled, single-pulse output mode) timing chart
RAMP1 instruction, S1 is specified as D0200, D1 is specified as internal relay M0050
RAMP
1
RAMP instruction
input
RAMP instruction input
Control direction
Pulse frequency
Reversible control
signal
Pulse output ON
Pulse output complete
Pulse output status
When the RAMP instruction input is on, pulses are output according to the settings configured by the control registers. The
reversible control signal is output from Q2. When pulse output starts, M0050 turns on. M0052 turns on while the pulse frequency
is increasing or decreasing. Pulses are output so that the frequency reaches the steady pulse frequency from the initial pulse
frequency in the frequency change time. When the frequency change time is specified as 100, the steady pulse frequency is
reached in 100 ms by increasing or decreasing the frequency every 10 ms.
Pulse output stops when the pulses configured by the preset value are output. (The number of pulses is also counted while
changing the frequency.) At this time, M0050 turns off and M0051 turns on.
If the RAMP instruction input turns off during pulse output, pulse output is canceled. If this input turns on again, the operation
starts from the beginning. Even if the contents of the data registers are changed during pulse output, the change is not reflected
in the pulse output operation. The changed content is reflected the next time the RAMP instruction is started.
18-22
S1
S2
D1
D0200
M0000
M0050
D0203
0 (Forward)
Q0
Q2
M0050
M0051
M0052
FC6A S
MICROS
ERIES
MART
L
P
M
ADDER
ROGRAMMING
ANUAL
1 (Reverse)
FC9Y-B1726