Note: The outputs (pulse output and reversible control output) used by RAMPL instruction cannot be used by other instructions simultaneously.
(12) Absolute position mode
Absolute position mode is always Enabled. Specify the target position with the preset value (13) for the X and Y axes.
Note: If the absolute position counter initialized flags in D8239 (absolute position control status) for the specified pulse outputs are 0 (not
initialized), a user program execution error will occur. After starting operation of the ladder program, execute the ABS instructions that correspond to
the applicable outputs one time.
(13) Preset value
Specify the target position. The number of pulses will be output in the amount of the target value. This value is the result of
subtracting the absolute position counter value from the target position. At that time, the pulses will be output by
automatically switching between forward for positive and reverse for negative according to the sign of the subtracted value.
(14) Current value
The number of pulses output is stored in the data registers. The current value is updated at each scan when the RAMPL