Error status
Outputs the error code that corresponds to the content of an error when there is an error in the settings. If a configuration
error occurs when a step starts executing, a user program execution error will occur, and the error code 20 is stored in
D8006.
Error Code
0
Normal
3
Preset value designation error
4
Steady pulse frequency designation error
5
Frequency change time designation error
7
Step options designation error
8
Next step number destination error
9
Interrupt number destination error
6. D2 (destination 2): Operation Status
D2 specifies the starting number of the internal relays to use with ARAMP1, ARAMP2, ARAMP3 and ARAMP4 instructions.
Starting from the specified internal relay, 5 sequential internal relays are used.
Specify the starting number so that the device range is not exceeded.
Address
Pulse output
Starting number+0
ON
Pulse output
Starting number+1
complete
Pulse output
Starting number+2
status
Starting number+3
Overflow
Pulse output
Starting number+4
direction
7. Preview
Displays a preview of the configured ARAMP instruction operation. The change in pulse output frequency, forward/reverse
operation, and the execution order of the steps can be checked.
The vertical axis indicates the pulse frequency and the horizontal axis indicates time.
The width of each step is locked, so the actual proportion of the horizontal axis is not accurate.
Status
0: Pulse output OFF
1: Pulse output ON
0: Pulse output not complete
1: Pulse output complete
0: Steady pulse output
1: Changing output pulse frequency
0: None
1: An overflow has occurred
0: Forward
1: Reverse
FC6A S
MICROS
L
ERIES
MART
The preset value was not set between 1 to 100,000,000.
All-in-One CPU module
CAN J1939 All-in-One CPU
module/Plus CPU module
The frequency change time was not set between 10 and 10,000.
The step options were not set to a valid value.
The next step number was not set between 0 and 18.
The interrupt number was not set between 1 and 18.
Description
This relay turns on during pulse output.
This relay turns off when the ARAMP instruction output stops.
This relay turns off when the specified number of pulses are
output and output ends
This relay turns on when pulse output completes.
This relay turns on when the step number currently being
executed is 0.
This relay turns off when the ARAMP instruction output starts.
This relay turns off when the pulse output status is steady.
This relay turns on when the pulse output is changing.
This relay turns on when the pulses output exceed the
configured preset value.
Pulse output continues even if an the overflow occurs during
steady output or while the pulse frequency is changing.
However, pulse counting (current value data register) is
suspended at the point when the overflow occurred.
This relay turns off when the output direction of the pulses
being output is forward.
This relay turns on when the output direction of the pulses
being output is reverse.
P
M
ADDER
ROGRAMMING
ANUAL
18: P
O
ULSE
UTPUT
Description
The steady pulse frequency
ARAMP1,
was not set between 15 and
ARAMP2
100,000.
The steady pulse frequency
ARAMP3,
was not set between 15 and
ARAMP4
5,000.
The steady pulse frequency
ARAMP1 to
was not set between 15 and
ARAMP4
100,000.
FC9Y-B1726
I
NSTRUCTIONS
18-51