4: B
I
ASIC
NSTRUCTIONS

AND and ANDN (And Not)

The AND instruction is used for programming a NO contact in a series. The ANDN instruction is used for programming a NC contact
in a series. The AND or ANDN instruction is entered after the first set of contacts.
Ladder Diagram
I0
I1
Q0
I0
I1
Q1
When both inputs I0 and I1 are on, output Q0 is on. When either input I0 or I1 is off, output Q0 is off.
When input I0 is on and input I1 is off, output Q1 is on. When either input I0 is off or input I1 is on, output Q1 is off.
Valid Devices
Instruction
I
AND
ANDN
30-10597
The valid device range depends on the FC6A Series MICROSmart type. For details, see "Device Addresses" on page 2-1.
Specify the bit by inserting a "." between the data register number and the bit position.

OR and ORN (Or Not)

The OR instruction is used for programming a NO contact in parallel. The ORN instruction is used for programming a NC contact in
parallel. The OR or ORN instruction is entered after the first set of contacts.
Ladder Diagram
I0
Q0
I1
I0
Q1
I1
When either input I0 or I1 is on, output Q0 is on. When both inputs I0 and I1 are off, output Q0 is off.
When either input I0 is on or input I1 is off, output Q1 is on. When input I0 is off and input I1 is on, output Q1 is off.
Valid Devices
Instruction
I
OR
ORN
30-10597
The valid device range depends on the FC6A Series MICROSmart type. For details, see "Device Addresses" on page 2-1.
Specify the bit by inserting a "." between the data register number and the bit position.
4-4
Program List
Instruction
LOD
AND
OUT
LOD
ANDN
OUT
Q
M
0-27
0-17
30-10597
10000-21247
Program List
Instruction
LOD
OR
OUT
LOD
ORN
OUT
Q
M
0-27
0-17
30-10597
10000-21247
FC6A S
MICROS
ERIES
Data
I0
I1
Q0
I0
I1
Q1
T
C
0-7997
0-1999
0-511
Data
I0
I1
Q0
I0
I1
Q1
T
C
0-7997
0-1999
0-511
L
P
MART
ADDER
ROGRAMMING
Timing Chart
ON
I0
OFF
ON
I1
OFF
ON
Q0
OFF
ON
Q1
OFF
R
0-225
10000.15-61999.15
Timing Chart
ON
I0
OFF
ON
I1
OFF
ON
Q0
OFF
ON
Q1
OFF
R
0-225
10000.15-61999.15
M