TADD (time addition) and TSUB (time subtraction) instructions add or subtract time data in two different modes. The data can be
selected from time (hour, minute, and second) or date/time (year, month, day, day of week, hour, minute, and second).
HTOS (HMS to s) and STOH (s to HMS) instructions perform conversion of time data between hours, minutes, seconds and
seconds.
HOUR (hour meter) instruction measures the on duration of the input and compares the total duration to a preset value. When the
preset value is reached, an output or internal relay is turned on.

TADD (Time Addition)

TADD
Mode
Valid Devices
Device
Mode
S1 (Source 1)
S2 (Source 2)
D1 (Destination 1)
For valid device address ranges, see "Device Addresses" on page 2-1.
When Mode 0 is selected, source devices S1 and S2 and destination device D1 occupy 3 consecutive data registers starting with the designated
device.
When Mode 1 is selected, source device S1 and destination device D1 occupy 7 consecutive data registers starting with the designated device.
Source device S2 occupies 3 consecutive data registers starting with the designated device.
Since the TADD instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
I
NSTRUCTIONS
S1
S2
D1
***
***
*****
Function
Selection of S1 data range
Date/time data to add to
Time data to add
Destination to store results
FC6A S
MICROS
ERIES
MART
S1 + S2 → D1, CY
When input is on, time data assigned by source device S2 are added to date/time data
assigned by source device S1, depending on the selected mode. The result is stored
to destination device D1 and carry (M8003).
I
Q
L
P
M
ADDER
ROGRAMMING
ANUAL
M
R
T
C
D
P
X
X
X
FC9Y-B1726
Constant
Repeat