IDEC MICROSmart FC6A Series Ladder Programming Manual page 554

Automation organizer windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

27: F
C
LOW
ALCULATION
Operation Example
To convert an analog input value from 0 to 4,095 to 0 to 65,535
Create the following ladder program.
SCALE(*) S1
M0000
(1) Specify D0000, where the analog input value is stored, for S1.
(2) Initialize the settings with the initialize pulse, and when M0000 turns on, the calculation is performed with the SCALE
instruction.
SCALE instruction settings
Devices tab
S1 (input value)
S2 (control register)
S3 (initialization input)
D1 (output register)
D2 (output relay)
Settings tab
Data type
Input maximum value
Input minimum value
Output maximum value
Output minimum value
Deadband
27-8
I
NSTRUCTIONS
S2
S3
D1
D0000
D0050
M8120
D0150
Settings
Settings
FC6A S
MICROS
ERIES
MART
D2
M0050
D0000
D0050
M8120
D0150
M0050
Word (W)
4,095
0
65,535
0
10