(4) D1 (Destination 1): Output Register
Specify the data register that will store the output value, the output value (dead band), and the amount of output change.
6 continuous words are used starting from the specified data register.
Storage
Destination
D1+0
Output value
D1+1
D1+2
Output value
D1+3
(dead band)
D1+4
Amount of output
D1+5
change
*1 The data range is 0 and 1.175494E-38 to 3.402823E+38.
(5) D2 (Destination 2): Output Relay
Specify the output or internal relay to store the output value (dead band) change notification and the input value alarm
output. 2 continuous words are used starting from the specified device.
Storage
Destination
Output value
D2+0
(dead band) change
notification
Input value warning
D2+1
output
(6) Device Allocation
Click this button to display the Device Allocation dialog box. As shown next, a table of the data registers and internal
relays and their corresponding SCALE instruction settings are displayed in the dialog box (7). Click Allocate Comments (8)
and you can configure the comments for the data registers and internal relays that correspond to the content of the settings.
Device Allocation dialog box
(8)
27-6
I
NSTRUCTIONS
Function
Stores the value after scaling with each scan.
If the dead band is disabled (dead band (S2+6, S2+7) is 0), the output value
(D1+0, D1+1) is stored in the output value (dead band) with each scan.
If the dead band is enabled (dead band (S2+6, S2+7) is not 0), output value
(dead band) change notification (D2+0) turns on and the output value (D1+0,
D1+1) is stored in the output value (dead band) only when the absolute value of
the difference between the output value (D1+0, D1+1) and the output value
(dead band) is greater than or equal to the dead band (S2+6, S2+7)) (difference
≥ dead band (S2+6, S2+7)).
For details, see "Dead Band Function" on page 27-2.
Stores the absolute value of the difference between the output value (D1+0,
D1+1) and the output value (dead band) (D1+2, D1+3).
Absolute value of difference
Output value (dead band)
Function
This relay turns on for one scan if the absolute value of the difference between the output value
(D1+0, D1+1) and the output value (dead band) (D1+2, D1+3) is greater than the dead band
(S2+6, S2+7). At that time, the output value (D1+0, D1+1) is stored in the output value (dead
band) (D1+2, D1+3).
This relay turns on when the input value (S1) is greater than the input maximum value (S2+0) or
when the input value is less than the input minimum value (S2+1). At that time, if the input value
(S1) is greater than the input maximum value (S2+0), it is scaled by the input maximum value
(S2+0). If the input value (S1) is less than the input minimum value (S2+1), it is scaled by the input
minimum value (S2+1).
(7)
FC6A S
MICROS
ERIES
Setting
(D1+4, D1+5)
Output value
(D1+2, D1+3)
(D1+0, D1+1)
L
P
MART
ADDER
ROGRAMMING
Setting
M
FC9Y-B1726
ANUAL
Data Types
F (float)
*1