Aramp (Ramp With Table) - IDEC MICROSmart FC6A Series Ladder Programming Manual

Automation organizer windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

18: P
O
I
ULSE
UTPUT
NSTRUCTIONS

ARAMP (RAMP with Table)

ARAMP
S1
1
*****
ARAMP
S1
2
*****
ARAMP
S1
3
*****
ARAMP
S1
4
*****
Frequency
Step 1
Before
Steady pulse
frequency
Frequency change time
When the initialization input specified by S2 is turned on, the initial values configured in the WindLDR ARAMP (Ramp Pulse
Output with Table) are stored in the control registers.
When the interrupt input specified by S3 is turned on, the step being executed is aborted and the interrupt step is executed.
The preset value and the steady pulse frequency for the running step are stored in the monitor registers specified by D1.
The control status including the pulse output status (output on/output direction/output complete) is stored in the operation status
specified by D2.
Notes:
If a pulse output instruction is simultaneously executed with the same output, a user program execution error will occur.
Error code 48 will be stored in D8006 and instructions that are executed later will be canceled.
The ARAMP instruction cannot be used in an interrupt program. If used in an interrupt program, a user program execution error will occur.
Error code 18 will be stored in D8006 and instruction execution will be canceled.
If a pulse output instruction is executed with the relay output type, a user program execution error will occur.
Error code 19 is stored in D8006 and instruction execution is canceled.
For details about the user program execution errors, see "User Program Execution Errors" on page 3-10.
Valid Devices
Device
S1 (Source 1)
S2 (Source 2)
S3 (Source 3)
D1 (Destination 1)
D2 (Destination 2)
*1 Special data registers cannot be used.
*2 Special internal relays cannot be used. Only 0 can be specified as the first digit of the internal relay number. 1 to 7 cannot be specified.
18-46
S2
S3
D1
D2
*****
*****
*****
*****
S2
S3
D1
D2
*****
*****
*****
*****
S2
S3
D1
D2
*****
*****
*****
*****
S2
S3
D1
D2
*****
*****
*****
*****
Step 2
Before
Steady pulse
frequency
Function
Control register
Initialization input
Interrupt input
Monitor register
Operation status
FC6A S
MICROS
ERIES
MART
The ARAMP instructions output pulses with the frequency change
function according to the information in the frequency table.
A frequency change and target frequency are set for each step, and the
pulse frequency is controlled through the combination of these steps.
When the number of pulses that were output reaches the preset value,
the next step that is specified for each step is executed. You can
configure a maximum of 18 steps.
The pulse output operation can be selected from the following two
operations with the step option settings.
The pulse frequency is changed at a constant rate until it reaches the
steady pulse frequency, and then a steady frequency of pulses is
output at the steady pulse frequency.
(Step 1 to 3 operations in the diagram below)
After outputting pulses that maintain the frequency in the previous
step, the frequency is changed at a constant rate until it reaches the
steady pulse frequency.
(Step 4 operation in the diagram below)
Step 3
Before
Steady pulse
frequency
I
Q
M
X
X
X
X
*2
X
L
P
M
ADDER
ROGRAMMING
ANUAL
Step 4
After
Frequency change time
R
T
C
D
P
Constant
*1
X
*1
X
FC9Y-B1726
Time
Repeat