IDEC MICROSmart FC6A Series Ladder Programming Manual page 155

Automation organizer windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

Example: ICMP>=
ICMP>=(W)
SOTU
I0
When input I0 is turned on, data of data registers D10, D11, and D12 assigned by source devices S1, S2, and S3 are compared. When the condition
is met, internal relay Q1 assigned by destination device D1 is turned on. When the condition is not met, Q1 is turned off.
S1
17
D10
>
15
D10
<
S1
S2
S3
D10
D11
D12
S2
S3
15
D11
D12
=
18
D11
D12
<
FC6A S
MICROS
ERIES
MART
D10 ≥ D11 ≥ D12 → Q1 goes on
D1
Q1
D1
15
Q1 goes on
19
Q1 goes off
L
P
M
ADDER
ROGRAMMING
ANUAL
6: D
C
ATA
OMPARISON
M8150
M8151
OFF
OFF
ON
ON
FC9Y-B1726
I
NSTRUCTIONS
M8152
M8004
OFF
OFF
ON
OFF
6-7