IDEC MICROSmart FC6A Series Ladder Programming Manual page 113

Automation organizer windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

CDPD (Double-Word Dual-Pulse Reversible Counter)
The double-word dual-pulse reversible counter CDPD has up and down pulse inputs, so the three inputs are required. The circuit
for a double-word dual-pulse reversible counter must be programmed in the following order: preset input, up-pulse input, down-
pulse input, the CDPD instruction, and a counter number C0 through C510, followed by a counter preset value from 0 to
4,294,967,295.
The preset value can be designated using a constant or a data register. When a data register is used, the double-word data of two
consecutive data registers becomes the preset value. For 32-bit data storage setting, see Chapter 5 "32-bit Data Storage Setting"
in the "FC6A Series MICROSmart User's Manual".
Ladder Diagram
Preset Input
CDPD
C2
100000
I0
Up Pulse
I1
Down Pulse
I2
I3
C2
Q1
Timing Chart
ON
Preset Input I0
OFF
ON
Up Pulse I1
OFF
ON
Down Pulse I2
OFF
Counter C2 Value
100000
ON
Counter C2
OFF
Program List
Instruction
LOD
LOD
LOD
CDPD
LOD
AND
OUT
• • •
• • •
0
99999
100001
100000
FC6A S
MICROS
L
ERIES
MART
• Double-word counter instructions use two consecutive
counters, and counters cannot be used more than once in
Data
a user program.
I0
• The preset input must be turned on initially so that the
I1
current value returns to the preset value.
I2
• The preset input must be turned off before counting may
C2
begin.
100000
• When the up and down pulses are on simultaneously, no
I3
pulse is counted.
C2
• The counter output is on only when the current value is 0.
Q1
• After the current value reaches 0 (counting down), it
changes to 4,294,967,295 on the next count down.
• After the current value reaches 4,294,967,295 (counting
up), it changes to 0 on the next count up.
• When power is off, the counter's current value is held, and
can also be designated as "clear" type counters using the
Function Area Settings (see Chapter 5 "Memory Backup"
in the "FC6A Series MICROSmart User's Manual".).
• Counter preset and current values can be changed using
WindLDR without downloading the entire program to the
CPU again. From the WindLDR menu bar, select Online >
1
100000
100000
Monitor > Monitor, then Online > Custom > New
Custom Monitor. To change a counter preset value,
select DEC(D) in the pull-down list box.
• When the preset or current value is changed during
counter operation, the change becomes effective
immediately.
• When power is off, the changed preset values are cleared
and the original preset values are loaded.
• For data movement when changing, confirming, and
clearing preset values, see "Changing, Confirming, and
Clearing Preset Values for Timers and Counters" on page
4-19.
• WindLDR ladder diagrams show CP (counter preset value)
and CC (counter current value) in advanced instruction
devices. The CNPD instruction cannot be used in an
interrupt program.
• If used, a user program execution error will result, turning
on special internal relay M8004 and the ERR LED on the
FC6A Series MICROSmart. For details about the user
program execution errors, see "User Program Execution
Errors" on page 3-10.
P
M
ADDER
ROGRAMMING
ANUAL
4: B
ASIC
FC9Y-B1726
I
NSTRUCTIONS