■ Ramp Table tab
12.
13.
14.
15.
16.
17.
12. Step numbers
This option selects the step number to configure. The output frequency error is ±5%.
13. Steady pulse frequency
This setting specifies the frequency at the steady output state before or after changing the frequency.
CPU Module Type
All-in-One CPU module
CAN J1939 All-in-One CPU module/Plus
CPU module
14. Frequency change time
This setting specifies the time to change the pulses.
Set this value in the range of 10 to 10,000 (increments of 1 ms).
The first digit of the setting is handled as zero. For example, if 144 is entered, the set value is handled as 140 ms.
15. Preset value
This setting configures the number of pulses to output from 1 to 100,000,000.
16. Step options
This setting configures the step direction and the execution timing of the change in the pulses.
Bit
15
14
13
12
Control direction
When reversible control is enabled, store 0 in this data register for forward operation and store 1 in this data register for reverse
operation.
Instruction
ARAMP1, ARAMP2
ARAMP3, ARAMP4
ARAMP1 to ARAMP4
Bit
Bit
11
10
9
8
7
FC6A S
MICROS
ERIES
MART
Set this value in the range of 15 to 100,000 (increments of 1 Hz).
Set this value in the range of 15 to 5,000 (increments of 1 Hz).
Set this value in the range of 15 to 100,000 (increments of 1 Hz).
6
5
4
3
Timing of change
0 : Before
1 : After
L
P
M
ADDER
ROGRAMMING
ANUAL
18: P
O
ULSE
UTPUT
Steady Pulse Frequency
Bit
2
1
0
Step direction
0 : Forward
1 : Reverse
FC9Y-B1726
I
NSTRUCTIONS
18-53