11. Alarm Value
Set the value that will be the trigger condition for Alarm Type (10). The value to set differs by the alarm type.
The content for the alarm value is as follows.
Alarm Type
Upper Limit Alarm
Lower Limit Alarm
Upper/Lower Limit Alarm
Upper/Lower Limit Range Alarm
Process High Alarm
Process Low Alarm
Upper Limit Alarm with Standby
Lower Limit Alarm with Standby
Upper/Lower Limit Alarm with Standby
*1 No alarm action when the alarm value is 0.
12. Hysteresis
Set the range from the alarm action point to when the alarm output changes from ON to OFF.
When hysteresis is set to a large value, the alarm output will not change by slight variations. When hysteresis is set to a small
value, the alarm output will change by slight variations near the alarm action point, which may negatively impact connected
equipment.
The range is 0.1 to 6,553.5 (°C/°F) or 1 to 65,535 (voltage/current input).
However, when the alarm type is Upper/Lower Limit Alarm or Upper/Lower Limit Alarm with Standby, you must set
hysteresis so that 1 ≤ hysteresis < Alarm Value (11) is satisfied.
13. Delay Time
Set the time until the alarm output is turned ON after the condition to turn the alarm output ON is satisfied.
The delay time prevents the alarm output from turning ON unintentionally when there are fluctuations in the process variable
due to the effects of noise.
After the condition to turn the alarm output ON has been satisfied, if it is no longer satisfied by when the delay time elapses, the
alarm output does not turn ON.
The range is 0 to 10,000 s. When 0, the delay time is disabled.
Set the deviation from the set point.
Set the value where the alarm will operate as
an absolute value.
Set the deviation from the set point.
Set the deviation from the set point.
FC6A S
MICROS
L
ERIES
MART
Alarm Value
P
M
ADDER
ROGRAMMING
ANUAL
19: PID C
ONTROL
Range
When the process variable is current/voltage
or a data register:
*1
-32,768 to 32,767
When the process variable is a thermocouple
or resistance thermometer and the data type
is set to Celsius or Fahrenheit:
*1
-3,276.8 to 3,276.7ºC/ºF
When the process variable is current/voltage
or a data register:
*1
0 to 65,535
When the process variable is a thermocouple
or resistance thermometer and the data type
is set to Celsius or Fahrenheit:
*1
0.0 to 6,553.5ºC/ºF
*1
Minimum to maximum
When the process variable is current/voltage
or a data register:
*1
-32,768 to 32,767
When the process variable is a thermocouple
or resistance thermometer and the data type
is set to Celsius or Fahrenheit:
*1
-3,276.8 to 3,276.7ºC/ºF
When the process variable is current/voltage
or a data register:
*1
0 to 65,535
When the process variable is a thermocouple
or resistance thermometer and the data type
is set to Celsius or Fahrenheit:
*1
0.0 to 6,553.5ºC/ºF
FC9Y-B1726
I
NSTRUCTION
19-11