(4) D1 (Destination 1): Status
Stores the status including the flow rate and the error during FLWP instruction execution. 16 continuous words are used
starting from the set device.
Storage
Function
Destination
D1+0
Flow rate
D1+1
D1+2
Operation status
D1+3
System work area
D1+15
*1 The upper and lower data registers change according to the 32-bit data storage method specified. For details, see Chapter 3 "Instructions
Reference" - "32-bit Data Storage" on page 3-9.
(5) D2 (Destination 2): Logged Data
Specify the device to store the data that is logged. A maximum of 212 continuous words are used starting from the set
device.
Note: The number of data registers that are used for logged data changes according to the maximum amount of logged data.
The number of data registers used for logged data is 2+6×the maximum amount of logged data.
Storage
Function
Destination
Amount of logged
D2+0
data
D2+1
Reserved
D2+2
D2+3
D2+4
Log
D2+5
1
D2+6
D2+7
D2+206
D2+207
D2+208
Log
D2+209
35
D2+210
D2+211
*1 The time expressed as the number of seconds from 00:00:00 on January 1st, 1970.
(For example, if the date/time is 00:00:00 on January 1st, 2015, the value is 1,420,070,400 seconds.)
*2 The upper and lower data registers change according to the 32-bit data storage method specified. For details, see Chapter 3 "Instructions
Reference" - "32-bit Data Storage" on page 3-9.
Stores the flow rate calculated every second. The flow rate unit
conforms to the K factor and flow rate unit settings.
Stores the status including the error during FLWP instruction execution.
Stores the amount of logged data that has been recorded.
When the log execution input (S3) changes from off to on
(during log updating), these devices store the content of special
Log time
data registers D8008 to D8014 (current calendar/time values)
converted to the number of seconds
When the log execution input (S3) changes from off to on
(during log updating), these devices store the accumulated flow
Accumulated
volume.
flow volume
For the processing when an accumulated flow volume overflow
or underflow has occurred, see "Carry and Borrow in Floating-
Point Data Processing" on page 3-8.
When the log execution input (S3) changes from off to on
Accumulated
(during log updating), these devices store the accumulated
time
time.
The unit is "s".
Log time
Accumulated
Same as log 1.
flow volume
Accumulated
time
FC6A S
MICROS
ERIES
MART
27: F
Description
Description
*1
from January 1st, 1970.
L
P
M
ADDER
ROGRAMMING
ANUAL
C
LOW
ALCULATION
:
F (float)
1.175494E-38 to 3.402823E+38
W (word): 0 to 35
D (double word):
0 to 4,294,967,295
F (float):
0, 1.175494E-38 to
3.402823E+38
D (double word):
0 to 4,294,967,295
Same as log 1.
FC9Y-B1726
I
NSTRUCTIONS
*1
Range
*2
*2
*2
27-25