IDEC MICROSmart FC6A Series Ladder Programming Manual page 443

Automation organizer windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

PID instruction dialog box configuration procedure
Use the default value for settings that are not described in this procedure.
1.
The Devices tab configures the devices used with the PID instruction.
• Set S1 (Control Register) to D0000 (1).
• Set S2 (Initialization Input) to M8120 (2).
• Set S3 (Control Relay) to M0000 (3).
• S4 (Set Point) is automatically set to D0007 (4).
Click the Input tab and configure the items.
2.
• For Process Variable (PV), select Analog Input, and then select AI002 (1).
• For Alarm 1, set the alarm value for the process high alarm to 250.0 (2).
For Alarm 2, set the alarm value for the process low alarm to 0.0 (3).
1.
1.
2.
2.
3.
FC6A S
MICROS
ERIES
MART
3.
4.
L
P
M
ADDER
ROGRAMMING
ANUAL
19: PID C
ONTROL
FC9Y-B1726
I
NSTRUCTION
19-53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents