11: W
P
EEK
ROGRAMMER
5. D1 (destination 1): Output
This setting configures the output for the results when the configured dates and the current date are compared.
Setting
Tag Name
Device Address
Comment
6. Pulse Output
This setting configures the operation for D1 (output). This setting is applied to all parameter tabs.
Selected check box
When the current date changes to the date in the ON settings, the output is turned on for only one scan.
Unselected check box
The output is turned on and off according to the ON settings and the OFF settings.
• Parameter tab
This tab configures the settings for the output. A maximum of 20 parameter tabs can be configured for 1 YEAR instruction.
3.
4.
1. Yearly
When Yearly is selected, the Month and Day settings are valid every year.
At this time, you can configure whether or not to make the Month and Day settings valid yearly from a year until another
year with Year.
2. Monthly
The settings for the selected tab are valid each month. At this time, Month is disabled.
3. ON settings
This section configures the date to turn on the output. The output is turned on at 0:00 on the configured date.
Setting
Year
Month
Day
Month and Day
Setting
Day of the week
End of month
11-18
I
NSTRUCTIONS
Specifies the tag name or the device address for each device.
Shows the device address that corresponds to the tag name.
Shows the comment for the device address. This item can be edited.
1.
2.
Specifies the year to turn on the output.
Specifies the month to turn on the output.
Specifies the day to turn on the output.
Specifies the day as the day of the week to turn on the output. Specify the week in
the range of the 1st to the 5th (or the last) week and set the day of the week.
Specify the end of month to turn on the output on the last day of the month.
FC6A S
MICROS
ERIES
MART
Description
Description
L
P
M
ADDER
ROGRAMMING
ANUAL
FC9Y-B1726
Range
2000 to 2099
1 to 12
1 to 31
1 to 6

Hide quick links: