To output 100,000 pulses with the frequency change function (reversible control by single-pulse output) from Q0
When the RAMP instruction input (I0) changes from off to on, pulse output starts. When I1 is off, the reversible control signal (Q2)
turns off (forward).
When I1 is on, the reversible control signal (Q2) turns on (reverse).
M8120
I0000
I0001
I0001
Setting
Function
Steady pulse frequency
Initial pulse frequency
Frequency change time
Frequency change curve
Reversible control enable
Control direction
Absolute Position Mode
Preset value
RAMP
S1
S2
1
D0000
M0000
MOV(W)
S1 -
D1 -
0
D0003
MOV(W)
S1 -
D1 -
1
D0003
Device Address
D0000, D0001
D0002, D0003
D0004
D0005
D0006, D0007
FC6A S
MICROS
L
ERIES
MART
Turn on initialization input (M0000)
M0000
When the RAMP instruction input (I0) turns on, pulse output
D1
starts
M0100
REP
When I1 is off, store 0 (forward) in control direction (D0003)
REP
When I1 is on, store 1 (reverse) in control direction (D0003)
Setting Value
1000
50
2000
Straight line
Single-pulse output
Forward
Disable
100000
P
M
ADDER
ROGRAMMING
ANUAL
18: P
O
ULSE
UTPUT
Details
1,000 Hz
50 Hz
2,000 ms
Forward=0
Preset value=100,000
FC9Y-B1726