IDEC MICROSmart FC6A Series Ladder Programming Manual page 286

Automation organizer windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

15: I
C
NTERRUPT
ONTROL
Programming WindLDR
In the DI (Disable Interrupt) or EI (Enable Interrupt) dialog box, select the check box on the left of Interrupt Groups 1 through 6
or Timer Interrupt to select source device S1. The example below selects interrupt groups 2, 3, and timer interrupt for the DI
instruction, and a 22 will be shown as source device S1.
15-2
I
NSTRUCTIONS
DI
FC6A S
MICROS
ERIES
MART
The total of selected interrupt inputs and timer interrupt
S1
is shown as source device S1.
22
L
P
M
ADDER
ROGRAMMING
ANUAL
Interrupt
Group 1 (I0)
Group 2 (I1)
Group 3 (I3)
Group 4 (I4)
Group 5 (I6)
Group 6 (I7)
Timer Interrupt
FC9Y-B1726
S1 Value
1
2
4
8
32
64
16