Error Status (S1+34, S1+35)
Indicates the PIDD error status.
Error Code
The analog input specified for Analog
101
Input is not configured.
PV Upper Range Value or PV Lower
Range Value is out of the range when
the PIDD instruction is started.
102
PV Upper Range Value or PV Lower
Range Value is set to an out-of-range
value while the PIDD instruction is being
executed.
An out-of-range value is set to MV High
103
Limit or MV Low Limit.
An out-of-range value is set to SP High
106
Limit or SP Low Limit.
Process Variable (PV) is set to a value
109
outside the range of PV Lower Range
Value to PV Upper Range Value.
The analog I/O module settings that were
111
set for Analog Output are incorrect.
Kp (Gain) is set to a value outside the
122
range of 0.00001 to 100.0.
Manual Mode Output MV is set to a value
130
outside the range of 0.0 to 100.0.
Control Period is set to a value outside
132
the range of 0.1 to 50.0.
Others
— Reserved —
S3: Control Relay
Storage
Destination
S3+0
Control Action
S3+1
Manual Mode Select
S3+2
Auto Mode Select
S3+3
Cascade Control Mode Select
S3+4
Manual Mode Active
S3+5
Auto Mode Active
Status Description
Function
0 (OFF): Reverse Control Action
1 (ON): Direct Control Action
Set to 1 (ON) to switch the PIDD instruction to Manual Mode. S3+1
automatically changes to 0 (OFF).
Set to 1 (ON) to switch the PIDD instruction to Auto Mode. S3+2
automatically changes to 0 (OFF).
Set to 1 (ON) to switch the PIDD instruction to Cascade Control
Mode. S3+3 automatically changes to 0 (OFF).
Changes to 1 (ON) while PIDD instruction is in Manual Mode.
Changes to 0 (OFF) when the mode is not Manual Mode.
Changes to 1 (ON) while PIDD instruction is in Auto Mode.
Changes to 0 (OFF) when the mode is not Auto Mode.
FC6A S
MICROS
ERIES
MART
Countermeasure
Check the analog I/O module settings.
Check if PV Upper Range Value or PV
Lower Range Value is set to an out-of-
range value, and check if PV Lower
Range Value ≥ PV Upper Range Value.
Check if MV High Limit or MV Low Limit is
set to an out-of-range value, and check if
MV Low Limit ≥ MV High Limit.
Check if SP High Limit or SP Low Limit is
set to an out-of-range value, and check if
SP Low Limit ≥ SP High Limit.
Check if the process variable is outside
the range of PV Lower Range Value to
PV Upper Range Value.
Check the analog I/O module settings.
Check the Kp (Gain) setting.
Check the value of Manual Mode Output
MV.
Check the control period settings.
Setting Details
L
P
M
ADDER
ROGRAMMING
ANUAL
19: PID C
ONTROL
Status
Classification
PID control
execution stops
PID control
execution stops
PID control
execution
continues
PID control
execution
continues
PID control
execution
continues
PID control
execution
continues
PID control
execution stops
PID control
execution
continues
PID control
execution
continues
PID control
execution
continues
R/W
R/W
R/W
R/W
R/W
R
R
FC9Y-B1726
I
NSTRUCTION
Error Check
with WindLDR
Yes
Yes
Yes
Yes
No
Yes
No
No
Yes
Modifiable
during
Execution
Yes
Yes
Yes
Yes
19-37