Xyfs (Xy Format Set) - IDEC MICROSmart FC6A Series Ladder Programming Manual

Automation organizer windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

16: C
OORDINATE
Introduction
This chapter describes the coordinate conversion
instructions that convert one data point to another
value using the linear relationship between the values
of X and Y.

XYFS (XY Format Set)

XYFS(*)
Valid Devices
Device
S1 (Source 1)
X0 through Xn
Y0 through Yn
For valid device address ranges, see "Device Addresses" on page 2-1.
When T (timer) or C (counter) is used as X0 through Xn or Y0 through Yn, the timer/counter current value (TC or CC) is displayed.
S1 (Format number)
Select a format number 0 through 7. A maximum of 8 formats for XY conversion can be set.
Xn (X value), Yn (Y value)
Enter values for the X and Y coordinates. Two different data ranges are available depending on the data type.
Data Type
Xn (X value)
Yn (Y value)
Valid Coordinates
Valid Data Types
W (word)
X
I (integer)
X
D (double word)
L (long)
F (float)
C
ONVERSION
.....
S1
X0
Y0
*
*****
*****
*****
Function
Format number
X value
Y value
Word
0 to 65,535
0 to 65,535
Y
65,535
0
When a bit device such as I (input), Q (output), M (internal relay), or R (shift register) is assigned as Xn or Yn, 16
points are used.
When a word device such as T (timer), C (counter), or D (data register) is assigned as Xn or Yn, 1 point is used.
FC6A S
MICROS
ERIES
MART
I
NSTRUCTIONS
(X0, Y0)
When input is on, the format for XY conversion is set. The XY
Xn
Yn
coordinates define the linear relationship between X and Y.
*****
No. of XY Coordinates
I
Q
M
R
T
C
X
X
X
X
X
X
X
X
X
X
X
X
–32,768 to 32,767
Y
32,767
0
X
–32,768
65,535
L
P
M
ADDER
ROGRAMMING
ANUAL
Y
(X1, Y1)
2 to 32
D
P
Constant
0 to 7
X
0 to 65,535
0 to 65,535
X
–32,768 to 32,767
Integer
0 to 65,535
X
65,535
FC9Y-B1726
(X2, Y2)
X
n
0 ≤ n ≤ 31
Repeat
16-1