Tml, Tim, Tmh, And Tms (Timer) - IDEC MICROSmart FC6A Series Ladder Programming Manual

Automation organizer windldr
Hide thumbs Also See for MICROSmart FC6A Series:
Table of Contents

Advertisement

TML, TIM, TMH, and TMS (Timer)

Four types of on-delay timers are available; 1-s timer TML, 100-ms timer TIM, 10-ms timer TMH, and 1-ms timer TMS. A total of
2,000 on- and off-delay timers can be programmed in a user program. Each timer must be allocated to a unique number T0
through T1999.
Timer
TML (1-s timer)
TIM (100-ms timer)
TMH (10-ms timer)
TMS (1-ms timer)
For details about device ranges, see "Device Addresses" on page 2-1.
To indirectly specify the value, specify it with a data register number, and specify the value of the data register in the range of 0 to 65,535.
TML (1-s Timer)
Ladder Diagram (TML)
TML
T0
4
I0
I1
T0
Q0
TIM (100-ms Timer)
Ladder Diagram (TIM)
TIM
T1
20
I0
I1
T1
Q1
TMH (10-ms Timer)
Ladder Diagram (TMH)
TMH
T2
100
I0
I1
T2
Q2
TMS (1-ms Timer)
Ladder Diagram (TMS)
TMS
T3
500
I0
I1
T3
Q3
Device Address
Range
T0 to T1999
0 to 65,535 s
T0 to T1999
0 to 6,553.5 s
T0 to T1999
0 to 655.35 s
T0 to T1999
0 to 65.535 s
Program List
Instruction
LOD
TML
LOD
AND
OUT
Program List
Instruction
LOD
TIM
LOD
AND
OUT
Program List
Instruction
LOD
TMH
LOD
AND
OUT
Program List
Instruction
LOD
TMS
LOD
AND
OUT
FC6A S
MICROS
L
ERIES
MART
Increments
1 s
100 ms
10 ms
1 ms
Timing Chart
Data
I0
I0
T0
T0
4
I1
I1
T0
Q0
Q0
Timing Chart
Data
I0
I0
T1
T1
20
I1
I1
T1
Q1
Q1
Timing Chart
Data
I0
I0
T2
T2
100
I1
I1
T2
Q2
Q2
Timing Chart
Data
I0
I0
T3
T3
500
I1
I1
T3
Q3
Q3
P
M
ADDER
ROGRAMMING
ANUAL
4: B
ASIC
Preset Value
Constant:
0 to 65,535
Data registers:
D0 to D7999
D10000 to D61999
ON
OFF
4 s
ON
OFF
ON
OFF
ON
OFF
ON
OFF
2 s
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1 s
ON
OFF
ON
OFF
ON
OFF
ON
OFF
0.5 s
ON
OFF
ON
OFF
ON
OFF
FC9Y-B1726
I
NSTRUCTIONS
4-7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents