27: F
C
LOW
ALCULATION
Log Output Function Overview
When the input is on, if the log execution input (S3) is turned on, the logged data (D2) is updated regardless of the enable
totalizer input (S2) on/off status. The maximum amount of logged data is 35 items.
When the enable totalizer input is off, totalization is paused. (The accumulated flow volume work area and the accumulated time
work area values are retained.)
Enable totalizer input (S2)
Log execution input (S3)
Flow rate
(S1+0, S1+1)
Accumulated flow volume work area
(D1+4, D1+5)
Accumulated time work area
(D1+6, D1+7)
Logged data (D2)
Note: For details on the log output function such as the operation immediately after the input is turned on, the operation when the enable totalizer
input (S2) is once again turned on, and the logged data updating when the log execution input (S3) is turned on, see "Log Output Function" on page
27-13.
Valid Devices
Device
S1 (Source 1)
S2 (Source 2)
S3 (Source 3)
D1 (Destination 1)
D2 (Destination 2)
Special data registers cannot be used.
27-10
I
NSTRUCTIONS
ON
Input
OFF
ON
OFF
ON
OFF
Sampling
period
Function
Flow rate
Enable totalizer input
Log execution input
Status
Logged data
FC6A S
MICROS
ERIES
MART
Update
I
Q
M
X
X
X
X
L
P
M
ADDER
ROGRAMMING
ANUAL
Update
R
T
C
D
P
Constant
X
FC9Y-B1726
Repeat