Timing Chart when the Input Turns On during the Configured Interval
When the input turns on or off during the interval between the ON settings and the OFF settings, and when the input turns on or
off after 0:00 on the date configured by the ON settings when pulse output is enabled, the timing chart is as follows.
• When pulse output is disabled
When the input is turned on, the current date and the ON and OFF settings are compared and the output turns on or off.
Settings
ON settings
OFF settings
Output port
[When the input is on before the day specified by the ON settings]
On February 13, 2012, when the input is turned on, the result of the current date compared with the ON and OFF settings is not
within the ON and OFF settings (February 15 to February 17, 2012). Therefore, the output remains off.
Current date
13th
ON
Input M0000
OFF
ON
Output Q0
OFF
Judgment
[When the input is turned on or off during the interval between the ON and OFF settings]
On February 15, 2012, when the input is turned on, the result of the current date compared with the ON and OFF settings is within
the ON and OFF settings (February 15 to February 17, 2012). Therefore, the output turns on. The output turns off when the input
is turned off.
On February 16, 2012, when the input is turned on, the result of the current date compared with the ON and OFF settings is that
the output is turned on.
Current date
13th
ON
Input M0000
OFF
ON
Output Q0
OFF
February 15, 2012
February 17, 2012
Q0
14th
ON settings
14th
ON settings
FC6A S
MICROS
ERIES
YEAR
M0000
February 2012
15th
February 2012
15th
Judgment
Judgment
L
P
MART
ADDER
ROGRAMMING
11: W
P
EEK
ROGRAMMER
S1
S2
S3
1
17th
16th
OFF settings
16th
17th
OFF settings
M
FC9Y-B1726
ANUAL
I
NSTRUCTIONS
D1
Q0
11-25