Stop Selection

It is possible to select deceleration stop or free-run stop according to the set deceleration time,
when a stop command is issued.
If operation is resumed during free-run operation, the Inverter will restart according to the
method set in Free-run Stop Selection (b088). For details, refer to "Deceleration Stop at Power-
off (Controlled Deceleration on Power Loss Function)" on page 5-106.
Parameter
No.
b091

Acceleration/Deceleration Time

Set an acceleration/deceleration time for the motor.
The set time indicates the acceleration/deceleration time from 0 Hz to the maximum frequency.
When the LAD (acceleration/deceleration) cancel (LAC) function is selected for a multi-
function input selection and the signal is turned ON, the acceleration/deceleration time
changes to the minimum acceleration/deceleration time (0.01 s) and the output frequency
instantaneously follows the set frequency.
You can also divide the acceleration/deceleration in two steps. For details, refer to "2-step
Acceleration/Deceleration Function (2CH)" on page 5-66.
Parameter
No.
F002/F202
F003/F203
P031
C001 to C007
Related functions
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Function name
00: Deceleration stop
Stop Selection
01: Free-run stop
Function name
Acceleration Time Setting
1/2
Deceleration Time
Setting 1/2
Acceleration/Deceleration
Time Input Type
Multi-function Input
Selection
Data
Data
0.01 to 3600.
Set the acceleration time from 0 to the
maximum frequency.
0.01 to 3600.
Set the deceleration time from the
maximum frequency to 0.
00: Digital Operator
03: Do not set.
46: LAC (LAD cancel)
A004/A204, P031, C001 to C007
5-2 Basic Functions
Default
Unit
setting
00
Default
Unit
setting
10.00
s
(30.00)
10.00
s
(30.00)
00
5-24