Setting the Acceleration/Deceleration Time

The following description provides information on parameters related to acceleration
and deceleration time settings.
Trapezoidal and S-shape acceleration and deceleration are available. Using the S-
shape characteristic function for acceleration and deceleration can reduce shock to the
machinery when stopping or starting.
H Setting the Acceleration/Deceleration Time (n16 through n19)
• Two acceleration times and two deceleration times can be set.
• The acceleration time is the time required to go from 0% to 100% of the maximum frequency and the
deceleration time is the time required to go from 100% to 0% of the maximum frequency. The actual
acceleration or deceleration time is obtained from the following formula.
Acceleration/Deceleration time = (Acceleration/Deceleration time set value)
Acceleration time 2 and deceleration time 2 are enabled by setting 11 for acceleration/deceleration time
selection in any of the n36 through n39 parameters for multi-function input.
Deceleration time 2 is also enabled by emergency-stop settings 19, 20, 21, and 22 in any of the n36,
n37, n38, and n39 parameters for multi-function input with n04 for interruption mode selection set to 0
(i.e., deceleration stop).
n16
Acceleration time 1
Setting
0.0 to 999 (s)
range
n17
Deceleration Time 1
Setting
0.0 to 999 (s)
range
n18
Acceleration Time 2
Setting
0.0 to 999 (s)
range
n19
Deceleration Time 2
Unit of
0.0 to 999 (s)
setting
Note Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz and 1-Hz increments if
the frequency is 100 Hz or over.
5-14
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
× (Frequency reference value) ÷ (Max. frequency)
Unit of
0.1 s
setting
(see note)
Unit of
0.1 s
setting
(see note)
Unit of
0.1 s
setting
(see note)
Unit of
0.1 s
setting
(see note)
Chapter 5
Changes during
Yes
operation
Default setting
10.0
Changes during
Yes
operation
Default setting
10.0
Changes during
Yes
operation
Default setting
10.0
Changes during
Yes
operation
Default setting
10.0

Advertisement

Table of Contents
loading

Table of Contents