7.10 Analog output

Goodrive35 series inverters have 2 analog output terminals (0 – 10 V or 0 – 20mA) and 1 high speed
pulse output terminal. Analog output signal can be filtered and the maximum and minimum values can
be adjusted. The analog output signals can be proportional to motor speed, output frequency, output
current, motor torque, motor power, etc. 100% of the output current is relative to 2 times of the rated
current of the inverter.
0
1
2
3
.
.
.
.
.
P06.00
(HDO output type selection)
.
0
19
1
20
0: open collector high speed
P06.00
pulse output
1: open collector output
Output instructions:
Name
frequency setting
frequency of HDI
Analog output selection
P06.14
(default value is 0)
P06.15
(default value is 0)
P06.16
(default value is 0)
P06.01、P06.02、P06.03、P06.04 output selection
0
Running frequency
3
Running rotation speed
6
Output voltage
9
Output torque
12
Analog AI3 input value
MODBUS communication
15
setting 2
Torque current (relative to the
18
nominal current of the motor)
Detailed instruction of
parameters
1: Counter input, high-speed
pulse counter input terminals
2:
Length
length counter input terminals
0.00 kHz – P05.43
-300.0% – 300.0%
P05.41 – 50.00 kHz
-300.0% – 300.0%
0.000s – 10.000 s
Analog output curve setting
P06.17
P06.18
P06.19
P06.20
P06.22
P06.23
P06.24
P06.25
P06.27
P06.28
P06.29
P06.30
1
Set frequency
Output current (relative to the
4
inverter)
7
Output power
10
Analog AI1 input value
13
HDI input value
PROFIBUS communication
16
setting 1
Exciting current (relative to the
19
nominal current of the motor)
157
Basic operation instruction
Default
value
counting
input,
0.00 kHz
50.00 kHz
100.0%
0.030 s
Analog output filter setting
P06.21
P06.26
P06.31
2
Ramp given frequency
Output current (relative to the
5
motor)
8
Set torque
11
Analog AI2 input value
MODBUS communication
14
setting 1
PROFIBUS communication
17
setting 1
20
Reserved
0.0%
AO1
AO2
HDO

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive 35 Series and is the answer not in the manual?

Subscribe to Our Youtube Channel

This manual is also suitable for:

Gd35-1r5g-4-c1Gd35-1r5g-4-d1Gd35-2r2g-4-c1Gd35-2r2g-4-d1Gd35-2r2g-4-h1Gd35-004g-4-c1 ... Show all

Table of Contents