Goodrive35 inverters
Code
Fault
Constant
OV3
overvoltage
Accelerating
OC1
overcurrent
Decelerating
OC2
overcurrent
Constant
OC3
overcurrent
Bus undervoltage
UV
fault
OL1
Motor overload
OL2
Inverter overload
SPI
Input phase loss
SPO Output phase loss
Rectifying module
OH1
overheated
Cause
 The acceleration or deceleration
is too fast
 The voltage of the grid is too low
 The power of inverter is too low
 The load transients or is
abnormal
 The grounding is short circuited
or the output is phase loss
 There is strong external
interference
 The overvoltage stall protection
is not open
 The voltage of the power supply
is too low
 The overvoltage stall protection
is not open
 The voltage of the power supply
is too low
 The motor setting rated current
is incorrect
 The motor stall or load transients
is too strong
 The acceleration is too fast
 Reset the rotating motor
 The voltage of the power supply
is too low.
 The load is too heavy.
 The motor power is too small.
 Phase loss or fluctuation of input
R,S,T
 U, V,W phase loss input (or
serious asymmetrical three
phase of the load)
 Air duct jam or fan damage
 Ambient temperature is too high.
to increase the energy consumption
components
 Install the brake components
 Check the setting of relative function
codes
 Increase the ACC time
 Check the input power
 Select the inverter with a larger
power
 Check if the load is short circuited
(the grounding short circuited or the
wire short circuited) or the rotation is
not smooth
 Check the output configuration.
 Check if there is strong interference
 Check the setting of relative function
codes
 Check the input power of the supply
line
 Check the setting of relative function
codes
 Check the power of the supply line
 Reset the rated current of the motor
 Check the load and adjust the torque
lift
 Increase the ACC time
 Avoid the restarting after stopping.
 Check the power of the supply line
 Select an inverter with bigger power.
 Select a proper motor.
 Check input power
 Check installation distribution
 Check the output distribution
 Check the motor and cable
 Refer to the overcurrent solution
 Redistribute dredge the wind
191
Fault tracking
Solution